KD-XHTZ Series Multi-tap Arc Suppressing Line Selection System

  • Summary
  • case
  • download

With neutral grounding via an arc suppression coil, the transient single-phase earth faults can be accurately identified to quickly enter and exit the offset mode. For non-instantaneous single-phase earth faults, the grounded lines can be accurately determined according to the set time to eliminate failed lines and improve the power supply reliability of the grid.

   

Technology Overview:
Our KD-XHTZ multi-tap arc suppression coil apparatus with automatic follow compensation contains the secondary paralleled damping resistor and perfect secondary protection technologies and is equipped with an advanced single-phase earth fault detector. It can perform real-time tracking of the grid capacitive current and rapid compensation of transient single-phase earth faults for troubleshooting. Moreover, it can also rapidly (less than 10s) identify non-instantaneous single-phase earth faults and trips (optional), and operate continuously under the grounding mode of conventional arc suppression coils. The secondary paralleled damping resistor technology applied in such apparatus avoids the easy burn-out case of the primary series resistor due to poor operating conditions. With higher safety and reliability, it proves to be an excellent automatic compensation apparatus of the grid neutral point.

  

Basic Parameters:
1. System voltage grade: 6 kV, 10 kV, 20 kV, 35 kV;
2. Current regulation range: generally 30%-100% rated current (upon customer's demand);
3. Current regulation mode: arithmetic adjustment; same differential current, small residual current (isometric adjustment upon customer's demand);
4. Grounding information recording: 200 times, power-off protection available;
5. Control mode: pre-setting;
6. Communication mode: RS232, RS485, optional baud rate range between 2,400-19,200 bps;
7. Communication protocol: standard MDOBUS and CDT communication protocols;
8. Cooling mode of primary equipment: AN or AF;
9. Protection grade of primary equipment: IPXX;
10. Working power supply:
AC: 220 V ± 10%, 50 HZ
DC: 220 V ± 10% or 110 V ± 10% (to be specified when ordering);
11. Number of lines selected: max. 40 pcs per unit (if line selection is needed, please specify when ordering)
    
Technological Advantages:
1. In this apparatus, the high-speed digital signal processor (DSP) is used as its control unit. The operating parameters of the system are visible on the large LCD and Chinese graphical operation interface.
2. For such apparatus, the application of new technologies, such as auto-tuning of secondary paralleled damping resistors, paralleled arc suppression coils for automatic tracking and measurement of capacitive current, and earth fault oscillographs, eliminates many technological difficulties, including multi-unit parallel operation and real-time measurement of capacitive current.
3. The small-perturbation line selection approach ensures the high accuracy in line selection, short perturbation time and less impact on the system.
4. We have been engaged in the grounding technologies of arc suppression coils for years, so we are quite skilled at the operation of such systems.

 

Related recommendations More
1999 - 05 - 09
Unit:
Product Description: Type KD-XH quick arc suppression system for distribution networks consists of a grounding transformer, arc suppression coils, a control cabinet and a central data display. The arc suppression coils are complete with primary and secondary windings, with 100% short-circuit impedance. The primary winding is connected to the neutral point of the distribution network as operating winding, while the secondary winding is connected backwards to two silicon controlled rectifiers (SCR) in parallel as control winding. The conduction angle of such SCR controller ranges between 0 and 1...
2001 - 05 - 10
Unit:
With neutral grounding via an arc suppression coil, the transient single-phase earth faults can be accurately identified to quickly enter and exit the offset mode. For non-instantaneous single-phase earth faults, the grounded lines can be accurately determined according to the set time to eliminate failed lines and improve the power supply reliability of the grid.   Technology Overview: Our KD-XHTZ multi-tap arc suppression coil apparatus with automatic follow compensation contains the secondary paralleled damping resistor and perfect secondary protection technologies and is equ...
2003 - 05 - 10
Unit:
With the recent development of distribution systems and further renovation of urban and rural distribution networks, numerous cables have replaced previous overhead transmission lines. To a certain extent, the decrease in the probability of single-phase earth faults reduces the high trip-out rate arising from low-resistance grounding systems. However, the high line selection accuracy of such low-resistance grounding systems are accepted by the majority of users. Consequently, they still have a wide range of applications in some urban distribution networks. Product Description: Such neutra...